QA16 Addressable Fire Alarm Control Panel

About the product





 


 
 
 


 


Characteristics





Each loop can connect up to 250 addressable devices. Maximum networking are 32 loops and total addressable points are 8000.
Large LCD screen (40 x 15 lines) allows more events to be displayed on the same screen.
Loop device can be set up to be temporarily isolated.
Individual loop module test feature to save time on panel test.
On-board Self-test feature for simulating alarm output.
Easy system programming through PC to panel.
Events log can store up to 2030 events.
Specification optional thermal printer that can printout complete panel status.





Specifications




Model

QA16



Power

220V AC 50/60Hz *Others also available



Battery Capacity

24V DC 4Ah



Charging Voltage, Current

26V DC 100~400mA *With auto adjustment function



Zone Voltage, Current

24V DC short circuit under 5V 30mA



System Capacity

250 devices/1 loop *Expandable for site requirement



Exterior Resistance

Round-trip under 40Ω



Transmitting Method

Digital series transmitting



Accumulation Time

0~40 seconds *Other options available



Main Sound

85dB @1M



# of conventional heat detectors connected

No limit *Except electronic-type



# of conventional smoke detectors connected

30/zone *Horing Lih's product



Material

1.6mm steel plate



Color

Pearl gray



Dimensions (mm) HxWxD

1~4 loop: 400x500x1305~8 loop:600x500x150









Approvalwww.askhitech.com








For more info visit www.fingerpak.com
Contact with supplier
BACK TO TOP