About the product
1 Zone
2~10 Zone
Characteristics
This unit has Accumulation function, it can minimize the false alarm that caused by unstable pulse or any abnormal signal ( false alarm ) and no effect on the function of fire alarm at all.
Each zone uses two different LED to indicate Fire alarm and Disconnection.
Zone test switch uses single-loop press type to improve the twisting switch that its contact failure will caused by dust and improper use.
Logical switch is different from traditional switch that needs to switch over higher voltage directly, it can prevent the damage caused by unstable voltage.
External indicator power-save device can select Light ON or OFF under normal condition during power-o-status, and stay blinking during alarm status which extend the operation life of control panel. (Prevent the control panel loss its function by wear-o-on battery under power-o-period)
Easy to switch from re alarm to smoke evacuation, sprinkling or foam system.
Movable zone indication labels, they can be easily changed without affect its magnificent appearance.
Annunciator is available on model AH-02124.
Specifications
Model
AH-00212 (1~10 zone)
AH-00212 (1 zone)
Power
220V AC/50Hz *Others also available
Battery Capacity
24V DC 1.2Ah
24V DC 0.8Ah
Charging Voltage, Current
26V DC 100~400mA *With auto adjustment function
Exterior Resistance
Round-trip under 50Ω
# of heat detectors connected
No limit *Except electronic-type
# of smoke detectors connected
30/zone *Horing Lih manufactured
Max. Output Current
1A
500mA
End of Line Resistor
10kΩ *One per zone
Material
1.2mm steel plate
Color
Ivory white *Others also available
Dimensions
350mm (H) x 285mm (W) x 105mm (D)
280mm (H) x 160mm (W) x 70mm (D)
Approval
Fore more info visit www.askhitech.com
www.fingerpak.com